Trend the pressure cascade, don't just alarm it
The typical differential between adjacent grades is 10–15 Pa, and alarms catch only the failure. A room pair drifting from 14 to 11 Pa has not alarmed, yet something changed. Plot the daily median of each differential against its commissioned value and review it weekly.