A pressure alarm tells you the cascade has failed. A trend tells you it started failing weeks earlier.
The typical differential between adjacent grades is 10–15 Pa, and Annex 1 guidance asks for at least 10 Pa. Most monitoring systems alarm somewhere near that floor, with a delay so door openings do not set it off. That catches the failure. It says nothing about the drift.
Take a room pair commissioned at 14 Pa that now sits at 11 Pa. No alarm, no deviation. Something has changed all the same: supply filters loading and cutting airflow, a door closer going soft, a return grille half-blocked by a trolley, a damper that moved, a new penetration nobody sealed. Each of those is cheap to fix now and expensive to explain after the alarm.
A trend makes the drift visible. Plot the daily median for each room pair against its commissioned value, and review it weekly. The median ignores door-opening spikes that the alarm delay is there to filter. A steady fall of a few pascals over a month is the signal to go looking.
The monitoring SOP should say who reviews the trend, how often, and what size of drift triggers a walk-down, as well as setting the alarm limits.