22 kV into a fab: power quality at the tool
IEEE 519 is measured at the point of common coupling, and a fab's tools sit far downstream of it. Harmonics from fan walls, pumps and chiller drives distort the shared LV bus. Separate tool transformers, DC chokes in the drive spec, filters sized from a study and a voltage THD check at each tool bus keep it off the tools.
InsightRead