A failing lithium-ion cell vents gas before it burns, mostly hydrogen, carbon monoxide, carbon dioxide and electrolyte solvent vapour.
The gas composition and the mixture's lower flammable limit usually come from UL 9540A cell testing. Hydrogen on its own is flammable from 4% by volume in air. Exhaust for battery enclosures is commonly sized on the explosion-prevention approach of NFPA 69, holding the space below 25% of the LFL, which for hydrogen means under 1%.
That target only helps if the fan is already running when the concentration starts to climb, so the sequence begins at the gas detector. Detectors go where the gas collects, high in the enclosure for hydrogen. The first gas alarm starts the exhaust, raises the fire alarm notification and tells the battery management system to isolate the affected rack and stop charging. Makeup air must not push gas into the room next door. Suppression release comes last, and the cause-and-effect matrix has to state beforehand whether the exhaust keeps running or shuts down when it does.
On many projects the detectors, fans, BMS and suppression panel come from four suppliers who each test their own part. The matrix that ties them together needs an owner, and the site test that proves it needs all four suppliers present.