BESS off-gas: ventilation before the fire

  • Renewable Energy
  • 1 min read

A failing lithium-ion cell vents gas before it burns, mostly hydrogen, carbon monoxide, carbon dioxide and electrolyte solvent vapour.

The gas composition and the mixture's lower flammable limit usually come from UL 9540A cell testing. Hydrogen on its own is flammable from 4% by volume in air. Exhaust for battery enclosures is commonly sized on the explosion-prevention approach of NFPA 69, holding the space below 25% of the LFL, which for hydrogen means under 1%.

That target only helps if the fan is already running when the concentration starts to climb, so the sequence begins at the gas detector. Detectors go where the gas collects, high in the enclosure for hydrogen. The first gas alarm starts the exhaust, raises the fire alarm notification and tells the battery management system to isolate the affected rack and stop charging. Makeup air must not push gas into the room next door. Suppression release comes last, and the cause-and-effect matrix has to state beforehand whether the exhaust keeps running or shuts down when it does.

On many projects the detectors, fans, BMS and suppression panel come from four suppliers who each test their own part. The matrix that ties them together needs an owner, and the site test that proves it needs all four suppliers present.

BESS thermal management and safety are part of our renewable energy work.

Related

More on this subject

Renewable energy suffers from a fatal flaw: Intermittency. The sun only shines during the day, and the wind is unpredictable. Relying on just one source often requires a massive, costly Battery Energy Storage System (BESS) to bridge the…

InsightRead

BESS thermal management, gas detection, explosion control and suppression often come from four suppliers, and each changes what the others must handle. Issuing the UL 9540A report with all four packages, naming one interface owner and choosing explosion control from the test data keeps them working as one system.

InsightRead

Hybrid renewable sites often size battery cooling from the weather and lump the other auxiliaries into one allowance. Resistive heat in the cells rises with the square of the current, and a 3% loss on a 1 MW discharge is 30 kW of heat. Control rooms, fire and gas safety and site services need their own lines.

InsightRead