Liquid-cooled BESS still needs an enclosure dew point

  • Renewable Energy
  • 1 min read

Liquid-cooled battery racks put 18 °C coolant pipes inside the enclosure, and outdoor air near 26 °C dew point enters at every door opening.

Most of the rack heat leaves in the coolant loop to a chiller or dry cooler outside. The enclosure HVAC is left with the residual: electronics, transformer losses, solar gain through the skin. On the load sheet the unit looks small. (Air-cooled racks put the whole cell heat into the room air instead, a bigger and mostly sensible load.)

The coolant pipes and cold plates, though, sit inside the enclosure at 18 °C, 8 K below that outdoor dew point. Any surface colder than the dew point of the enclosure air collects water.

Each door opening for maintenance swaps part of the enclosure air for outdoor air at about 26 °C dew point, and the pipes sweat until the unit has dried it back down. A unit picked on the residual heat alone may have little latent capacity left for that recovery.

In the enclosure specification this becomes a dew point limit set a margin below the coldest pipe temperature, checked against peak outdoor dew point with the door openings counted in the load.

Our renewable energy work covers BESS thermal management and safety.

On liquid-cooled systems, who in your team owns the enclosure dew point?

Related

More on this subject

Many investors mistakenly view a Battery Energy Storage System (BESS) as merely a giant "backup generator" or a passive power bank. This view overlooks its true potential. In reality, BESS is a powerful financial and engineering…

InsightRead

Engineering's part of the product quality review

The 2013 text of EU GMP Chapter 1 lists the qualification status of relevant equipment and utilities among the items a product quality review should include. Engineering can make that line believable with four more inputs: changes in the period, excursions and trends, calibration and maintenance failures with product impact, and the status of engineering CAPAs.