Two swapped sensor cables pass the checks made from the desk. A point-to-point loop check finds them: identify the device by tag, follow the wiring to its I/O channel, apply a known input at the device, confirm value, unit and tag on the graphic, trend and alarm, then sign the loop sheet.
A fire damper that drops on a failed fusible link cuts the supply to a branch while the AHU still shows healthy on the BMS. Each damper needs an access door on the side the link is reset from, a closed-position switch wired to the BMS, and a recorded test on the fire code's interval.
"Like-for-like" is a conclusion that needs evidence. Before a replacement fan, FFU or AHU is fabricated for a validated suite, compare the measured duty point, filters and seals, connections, control points and clean-zone materials with the installed item, and let QA decide in change control.
Environmental monitoring and BMS data that support GMP decisions must meet ALCOA+. In practice that means individual logins, time-synchronized controllers, an audit trail users cannot disable, alarms acknowledged with name and comment, and tested backups, with GMP-critical parameters separated early onto a validated system.