Company news from Humiley Group INC and technical notes on cleanroom HVAC, GMP validation, semiconductor environments and energy-storage engineering.

  • 780 articles

News

News

209 articles filed under News.

A gowning room can pass OQ and fail its first full shift change when the shift change was never in the URS. In the V-model each stage on the right proves a document on the left, so operating scenarios such as operators per shift change and door openings per hour belong in the URS as numbers.

InsightRead

A fan offered at 45 mmAq and 50 m³/min against a schedule of 450 Pa and 3,000 m³/h matches on airflow and is about 2% short on pressure. The bigger check is the basis: schedules state external static pressure, while some datasheets give total pressure before the unit's internal losses.

InsightRead

A month-end note from Tony Nguyen, CEO

After more than twenty years with automation vendors and running an EU-GMP EPC contractor, Tony Nguyen saw problems start at the handovers between companies rather than inside any one scope. This note explains why Humiley is organized as one accountable team across design, project management, equipment and maintenance.

InsightRead

EN 1886 class L2 allows an AHU casing 0.44 l/s per m² of leakage at −400 Pa. On a witnessed FAT, casing leakage, fan airflow at design static pressure, filter bypass and the control panel are checked against the approved specification, and both engineers sign the sheet that goes into the equipment file.