02:14, night shift. A Grade B pressure alarm is acknowledged under the login "operator". Nobody can say who that was.
That one line is a data integrity finding. EMS and BMS data that support GMP decisions have to meet ALCOA+: attributable, legible, contemporaneous, original and accurate, plus complete, consistent, enduring and available. On a facility system those words become design requirements:
- Attributable: individual user accounts with role-based access. No shared "operator" or "admin" logins.
- Contemporaneous: controllers and servers time-synchronized, so an alarm on the PLC and its record on the server carry the same time.
- Original and complete: an audit trail that records who changed a setpoint or alarm limit, from what, to what, when and why, and that users cannot switch off.
- Alarms treated as records: acknowledgement with user, time and comment, and alarm delays that are justified rather than left at default.
- Enduring and available: backups with a tested restore, and retention that matches your record-keeping rules.
Decide early which parameters are GMP-critical. Those belong on a validated EMS; the rest can stay on the BMS without dragging it into full Part 11 and Annex 11 validation.
Humiley designs automation and SCADA to 21 CFR Part 11 and EU Annex 11 on Rockwell, AVEVA, COPA-DATA and Ignition platforms.