Either way an FFU filter is changed, the room stops for the room-side leak scan, cleaning and recovery. Top-side replacement needs a walkable ceiling and disturbs the plenum; room-side replacement brings the loaded filter out through the classified space. Both need upstream injection and sampling ports that can be reached.
A standby generator run with no load each month proves that it starts. NFPA 110 sets the monthly exercise for diesel sets at a minimum of 30 minutes, at not less than 30% of nameplate kW or at the exhaust temperature the manufacturer recommends. Record load, time and temperatures at every run.