Idling a standby diesel generator for half an hour every month slowly fouls its injectors.
The no-load run does show that the set starts. But a diesel running light never reaches working temperature. Fuel burns incompletely, and carbon and unburned fuel build up in the exhaust and on the injectors. Engine people call it wet stacking. The set that has started faithfully every month is then asked for full load on the day the grid fails.
NFPA 110, the US standard for emergency and standby power systems, sets the monthly exercise for diesel sets at a minimum of 30 minutes, in one of two ways: at a load that holds the exhaust gas temperature the manufacturer recommends, or at operating temperature and not less than 30% of the standby nameplate kW rating.
Thirty percent is a floor. On a pharmaceutical site the better test transfers the real load, AHUs, chillers, BMS and cold rooms, with the transfer switch doing its job.
Whatever the load, write it down: kW carried, minutes run, coolant and exhaust temperatures, oil pressure.
When did your generator last carry 30% for half an hour?




