ISO 13485 §6.4.2 asks for documented contamination control without naming a cleanroom class. Setting the class from sterilisation method, patient contact and bioburden sensitivity often lands device assembly at ISO 8, with ISO 7 only where needed, less air than Grade C, a smaller AHU and a reason an auditor can read.
A Vietnamese manufacturer can reach the EU market by acquiring a marketing authorisation and transferring the site, by new registration via technology transfer, or by in-house development. All three need an EU GMP site and quality system, an EU-based MAH, a Qualified Person and pharmacovigilance.
EU GMP Annex 1 (2022) clause 6.13 expects sampling at all outlets and points of use, worst-case locations considered, and a representative sample of manufacturing water every day. That only works if reachable sample valves, sub-cooler outlets, the loop return and flushing drains are on the P&ID before isometrics.
EN 1886 class L2 allows an AHU casing 0.44 l/s per m² of leakage at −400 Pa. On a witnessed FAT, casing leakage, fan airflow at design static pressure, filter bypass and the control panel are checked against the approved specification, and both engineers sign the sheet that goes into the equipment file.
A catalogue AHU suits an office zone or a like-for-like swap. Where humidity is specified it needs checking: a room at 20 °C and 45% RH has a dew point of about 7.7 °C, and a range coil can meet total kW yet leave the air wetter. Ask for leaving-air dew point at the site's peak condition.
Near the sea or heavy industry, condensate turns a copper-tube, aluminium-fin coil into a galvanic cell and the fin bond fails first. Coatings applied after assembly cover the cut edges that pre-coated fin stock leaves bare and the collars where its coating cracks. Select the coil with the maker's correction factor and ask for the salt-spray report.
A FAT witness needs the approved drawings and datasheets at the order revision, the approved protocol with numeric criteria, the specification clause list, the expected test instrument list and an agreed punch-list format with someone authorised to sign it. Without these, a witness can only watch.
Ducted terminal HEPA and FFU ceilings can both reach Grade B or C. A ducted system sets airflow at one AHU fan; an FFU ceiling has many settings to hold, but a single failure stays local. Energy depends on fan efficiency and duct losses, so calculate it for the layout.
Low-level returns sweep particles down and out past the work, but each grille needs a riser to the ceiling void. Some modular wall systems can carry it inside the panel, flush with the room; ask before the layout is drawn. Use tool-free grilles, spread returns along the walls and seal the joints.
Masonry with epoxy paint is cheaper to build, but every later penetration in a classified room means drilling, repainting, cleaning and a particle count under change control. Before choosing, count how often each type of room in your current plant changed in the last five years; rooms that changed more than once usually repay panels.
Under EU GMP Chapter 4, paragraph 4.11, a product with a 5-year shelf life keeps its batch documentation for at least 6 years. Environmental and BMS data that supported release is safest kept for the same period, so historian retention and storage belong in the URS for the BMS and EMS.