Sold as an energy saver, a capacitor bank leaves the kWh meter almost where it was.
The bank supplies reactive current next to the load, so the grid no longer has to. The motors, fans and chillers draw the same kilowatts as before, and a meter that barely moves is giving the correct reading.
The energy saved is copper loss upstream of the bank, in the incoming cable and the transformer: their current falls, and the loss goes with its square. Correct a load from a power factor of 0.75 to 0.95 and the upstream current drops to 79% of what it was, the loss to about 62%. If that loss was 2% of the energy, the saving is under 1% of the kWh. Cables downstream of the bank carry what they carried before.
The payback comes from the tariff and the transformer. In Viet Nam the utility bills reactive energy when the average power factor is below 0.9, as a percentage added to the active energy charge that grows as the power factor falls. Correction removes that charge. It also frees transformer capacity: 400 kW takes 533 kVA at 0.75 and 421 kVA at 0.95.
A bigger bank saves little more: above 0.9 there is no reactive charge left to remove, and an oversized fixed bank pushes the power factor leading at light load. With drives on the same board, plain capacitors can also resonate with their harmonics, so the choice of detuning reactors belongs to a harmonic study.