Last year's cooling coil detail is on this year's drawing, still sized for last year's air.
It gets reused because it worked. On that job the coil saw mostly recirculated air; here it sits in a 100% outdoor air unit, where on a wet afternoon most of the load is latent. With the same rows and a different entering condition, the coil can meet its sensible capacity and still leave the supply air too wet.
The drawing came out of a requirement and a calculation, and only the drawing gets copied. Before reusing a detail, find the design basis it came from. Mark what is different on this job (entering air, water temperature, airflow, the room it serves) and rerun the calculation. Then write the source on the calculation, so the next engineer can see whether a number was derived here or inherited.
A junior engineer rarely asks a senior where a detail came from unless the question is treated as normal. At Humiley, cross-functional training comes with on-the-job mentoring by senior leads.
Which detail in your standard library can no longer be traced back to a calculation?