"Decide on filtering from a harmonic study" is one line in a specification. The study behind it has five parts.
We write that line ourselves, so this is what we expect the study to contain.
- Collect the single-line diagram, the transformer data and the short-circuit level at the point of common coupling (PCC). IEEE 519-2022 sets its current limits as total demand distortion (TDD), and the limit depends on the ratio of short-circuit current to maximum demand load current. Without the fault level there is nothing to compare with.
- List the non-linear loads: drives, EC fans, UPS, rectifiers. Ask each vendor for the harmonic current spectrum with the choke actually fitted. A 6-pulse EC fan sits around 35–42% THDi with a DC choke and 65–75% without.
- Measure the existing distortion where the site is live. Background voltage distortion from the grid and the neighbours is there before the new load is.
- Model the network and compare the result at the PCC with the voltage distortion and TDD limits, for the load cases that will occur. Include generator supply: a generator has a far lower fault level than the grid, so the same currents distort its voltage more.
- Select the mitigation, install it, then measure again and keep the report.
Step 5 is the one most often dropped, and it is the only one that shows the model was right.
Our own design target is THDi ≤ 5% at the PCC. In Viet Nam, Circular 05/2025/TT-BCT applies as well.