A walk-on cleanroom ceiling turns the void into a service floor, so dampers, sensors, cables and lighting are maintained without entering the room. It only helps filter changes if the HEPA housings are top-serviceable, and the void must be designed as a floor. Worth it for plant-heavy suites, rarely for small labs.
A 50 mm clash tolerance hides a duct running 40 mm into a beam. Pipes and ducts modelled at bare size leave no room for insulation, and trade pairs that were never run never appear. A zero-clash report should state its tolerance, the pairs tested and what each model leaves out.
When 5% of a 10,000 m³/h, 12 °C supply leaks into a 32 °C ceiling void, about 3.4 kW of sensible cooling goes with it and the room is 500 m³/h short. A named airtightness class, a pressure test before insulation and sealed joints and access doors keep that cooling in the duct.