Installing terminal HEPA filters: the sequence
A terminal HEPA filter passes its factory test and is then carried through a building site. Clean the room and run on pre-filters first, unpack at the point of use, check the label against the position schedule, tighten evenly, then leak-scan the installed filter to ISO 14644-3 and record the serial number against its position.