Installing terminal HEPA filters: the sequence

  • Maintenance Service
  • 1 min read

Every H14 filter is leak-tested at the factory and ships with its own test report. The next test it gets is in the ceiling.

Between those two tests come the truck, the store, the corridor and a ladder, and the media is a pleated glass-fibre paper that a fingertip goes straight through. Most of the damage happens in the last two metres: a thumb in the pleats, a gasket rolled on one side, a frame pulled down unevenly.

The sequence that avoids it:

  1. Clean the room and the housings, then run the system on its pre-filters, so the new HEPAs do not load up with construction dust.
  2. Unpack each filter at its point of use and carry it by the frame. Inspect both faces of the media and the whole gasket under a torch.
  3. Check the label against the position schedule: size, class, rated airflow, serial number.
  4. Seat the filter and tighten the clamps evenly, to the compression the manufacturer gives.
  5. Leak-scan the installed filter across the face and around the perimeter (the installed filter system leakage test of ISO 14644-3), and record the serial number against the ceiling position.

The in-place scan covers the seal and the frame as well as the media, which the factory test cannot do.

Reseating normally cures a leak at the gasket, which is an installation fault. A leak in the media usually means a new filter, so keep a spare of each size on site until the scan is finished.

Related

More on this subject

ISO Class 1 vs ISO 5: counting at 0.1 µm

ISO Class 1 allows 10 particles of 0.1 µm and larger per cubic metre; ISO 5 allows 100,000 at that size. At that level the installed leak scan must prove frames and grid, not just the U15 filter, single-digit counts need large sample volumes, and airborne molecular contamination needs its own sampling plan.

InsightRead

Open ductwork on site and short-lived terminal HEPAs

Construction dust left in supply ducts ends up in the terminal HEPA filters, which then load in months. Order ductwork factory-cleaned and capped, store it off the floor, re-cap every open end at the end of each shift, inspect and wipe each section before connection, and fit the terminal filters last.

InsightRead