After more than twenty years with automation vendors and running an EU-GMP EPC contractor, Tony Nguyen saw problems start at the handovers between companies rather than inside any one scope. This note explains why Humiley is organized as one accountable team across design, project management, equipment and maintenance.
Where a SCADA, BMS or EMS records GMP-relevant data, access control, clock synchronization, alarm records and audit trails are decided by the electrical and automation engineers. Many sites keep those parameters on a separate validated EMS. Humiley's cross-functional training covers GMP, validation and project management.
EU GMP Annex 15 allows some FAT results to be used at IQ and OQ when transport and installation do not affect them. For an AHU that means listing what the trip can change, from fan alignment to software version, retesting those on site and referencing the rest.
In ISO and IEC standards, shall states a requirement, should a recommendation, may a permission and can a possibility. Normative annexes bind; nothing in an informative annex, a note or an example has to be met to claim conformity. EU GMP is different: it is written in 'should' and still expected. Check the verb and the annex before quoting a clause.
Bracketing, as ICH Q1D (2002) defines it, tests only the extremes of a design factor such as strength or container size at all time points and assumes they represent the levels between. Three strengths in two bottle sizes still leave four of six combinations on test, and any reduced design should be justified.