Shared SCADA logins and PLC clocks a few minutes apart are inspection findings that start on the electrical side of a project.
Alarm acknowledgements with no user name against them belong on the same list.
Where a SCADA or BMS records GMP-relevant parameters, such as room differential pressures or the temperature and humidity used in batch decisions, it falls under 21 CFR Part 11 and EU GMP Annex 11. Many sites keep the BMS non-GMP and put those parameters on an independent, validated EMS. Whichever system carries them needs secure, time-stamped audit trails, controlled access to setpoints, and records that are attributable and cannot be changed without a trace.
In practice that means user accounts and access levels in the SCADA configuration, and time synchronization across controllers so that events from two PLCs line up in the audit trail. QA and the automation engineer have to agree which alarms are GMP-relevant and how each acknowledgement is recorded. Someone also has to decide what happens to data when a PLC or network switch loses power, and how much the controller buffers until the server is back.
Left at controller defaults, those decisions produce the findings above.