Photometer or particle counter for the HEPA leak scan
ISO 14644-3 allows installed filter leak scans by aerosol photometer or discrete particle counter. The photometer is quick but needs roughly 10 to 100 mg/m³ upstream; the counter works at far lower loads. For ULPA and filters you want kept free of oil, choose the counter method at design stage.