The revised EU GMP Annex 1 has applied since 25 August 2023. Its one delayed point, 8.123 on lyophilisers, followed on 25 August 2024.
It was published on 25 August 2022 with a one-year transition. Inspectors read it as the current text, and a site master plan that still says "Annex 1 gap assessment: planned" is more than three years past the date the annex applies from.
Starting late mainly changes the order of work. Run the assessment against the actual text, clause by clause, and date each finding as it is written. Then rank the actions by contamination risk rather than by how quickly they close, with an owner against each one.
Most findings end up in the Contamination Control Strategy. Annex 1 expects it to tie airflow, material and personnel flows, barriers, utilities, monitoring and qualification into one argument, and gaps appear where that argument breaks. A typical break: the CCS names the pressure cascade as a control and the design holds at least 10 Pa between grades, but the alarm delay in the monitoring system was set at commissioning and nobody can show why that delay is acceptable. Closing it takes a written rationale, a test of the alarm and a change to the SOP.