Annex 11 asks for periodic evaluation. Many sites answer it by re-running the OQ, which is a lot of work for the wrong question.
The clause asks whether the system is still in a valid state and still compliant. It names what to look at: functionality, deviations, incidents, problems, upgrade history, performance, reliability, security and validation status. The evidence sits mostly in records that already exist: change control since the last review, deviation and incident reports, open problems, the upgrade log, user access reviews for security, and the current validation status. Put together and read by someone who understands the system, those records answer the question.
Requalification is different. Annex 15 section 4 expects equipment, facilities, utilities and systems to be evaluated at an appropriate frequency to confirm they remain in a state of control. For a BMS or EMS that can mean a retest, and the review is what should set its scope.
In practice, do the review first and decide afterwards. If three firmware updates went through change control with regression testing, and no deviation or incident touched the system, the evaluation can close with a signed report. If an upgrade skipped testing, retest the functions it touched.
Our automation work is designed to 21 CFR Part 11 and Annex 11, and periodic requalification and calibration are part of our maintenance service.