Class 100 is ISO 5, and 209E is long gone

  • Life Sciences
  • 1 min read

People still write "Class 100" into URS documents, more than 25 years after the standard that defined it was cancelled.

FED-STD-209E was cancelled in 2001 and replaced by ISO 14644-1. Its classes counted particles of 0.5 µm and larger per cubic foot. Class 100 meant 100 per cubic foot.

ISO 14644-1 counts per cubic metre, at several particle sizes. One cubic metre is about 35.3 cubic feet, so 100 per cubic foot is roughly 3,530 per cubic metre, which is why ISO 5 sits at 3,520 at 0.5 µm.

The FDA's 2004 aseptic guidance still prints both names side by side: Class 100 is ISO 5, Class 10,000 is ISO 7, Class 100,000 is ISO 8, all measured in operation. That table is where most of the old names survive.

The mapping is clean only at 0.5 µm and only when the occupancy state is stated. "Class 10,000" says nothing about at rest versus in operation, and nothing about the EU grade. Written into a URS for an EU market, it leaves the designer to guess between a Grade B background and a Grade C room.

Our suggestion: write the ISO class, the particle size, the state and the EU grade where it applies. "ISO 7 in operation, Grade B" leaves nothing to guess.

How we work on this

Industries

Related

More on this subject

CPV: one abbreviation, two different things

Continued process verification is the FDA's Stage 3: assurance during routine production that the process remains in a state of control. EU GMP Annex 15 (2015) calls it ongoing process verification. Continuous process verification, defined in ICH Q8(R2), is an alternative approach to validation. Write the phrase out and cite its source.

InsightRead

CSV vs CSA on one BMS alarm function

Scripted CSV evidences every step of a BMS pressure alarm test. FDA's Computer Software Assurance guidance keeps scripted tests for high-risk checks such as setpoint, delay and the audit record, then adds unscripted testing of failure modes, recorded by what was tried and what happened.

InsightRead

At 20 air changes an hour, ideal mixing gives a 100:1 recovery time of about 14 minutes; a poorly mixed corner acting like 10 ACH takes about 28. Swirl diffusers come closest to ideal, perforated faces mix less, and plain HEPA faces suit a critical bench. Place the recovery probe where air arrives last.