A 0.4% design condition is exceeded about 35 hours a year. That number is a decision, and most design bases never state it.
ASHRAE climatic design data lists outdoor conditions by annual frequency of occurrence: 0.4%, 1% and 2%. They are not safety margins. They count hours. Over the 8,760 hours in a year, 0.4% is about 35 hours, 1% is about 88 and 2% is about 175. On those hours the outdoor air is worse than the value the coil was sized for.
For an office, 175 warm hours is a comfort complaint. For a room with a validated RH limit it can be a run of excursions, and they cluster: the hours above design arrive together, on the wettest afternoons of the season.
Two details matter in a tropical climate. First, read the right column. The dehumidification design dew point, not the cooling dry-bulb, is what sizes a fresh-air coil for humidity. Second, choose the percentile per room, not per project. A warehouse may live with 2%. A suite handling hygroscopic powder probably wants 0.4% and a margin on the latent load.
Writing the percentile into the design basis turns an assumption into something QA can review and sign.