Copy a GMP air handler from a Ho Chi Minh City plant to a site near Hanoi and it can arrive with no heating coil and no humidifier.
In the south that is correct. Outdoor air stays warm and humid all year, and the design problem is taking moisture out. In the north, the winter monsoon brings cold, dry air for weeks at a time, and a 100% fresh-air unit, or one with a large fresh-air share, has to deal with it.
ASHRAE's climatic design tables have a column for each part of this, and each sizes a different component:
- Heating dry-bulb, 99.6% or 99%. Sizes the preheat coil, so fresh or mixed air reaches the cooling coil and the room above the lowest temperature you allow.
- Humidification dew point, 99.6% or 99%, with its coincident dry-bulb. Sizes the humidifier, if any room has a lower RH limit. Rooms held above a minimum RH for static control, or for gelatin capsules that turn brittle, are the usual cases.
- The dehumidification columns, which still size the cooling coil. The north has a wet summer too, and a humid spring when cold walls and floors sweat.
Take the station nearest the site from the current Handbook and use its numbers rather than a rule of thumb. If no room has a lower RH limit, record that in the design basis so the missing humidifier is a documented decision.