At 1,500 Pa and 60% overall efficiency, the supply fan warms the air by about 2 K before it reaches the room.
With the motor in the airstream, as in a plug fan or an EC fan wall, every watt drawn ends up as heat in the air. The energy balance is short: ΔT = Δp / (ρ·cp·η). With 1.2 kg/m³ and 1,005 J/kg·K, that is 1,500 / (1.2 × 1,005 × 0.6), or 2.1 K. On a 20,000 m³/h unit it comes to roughly 14 kW.
Where the fan sits decides where that heat goes. Draw-through, after the coil, it arrives in the room: a coil that leaves air at 13 °C delivers it at about 15 °C, and a load sheet that forgot the fan gets a warm room. Blow-through, ahead of the coil, the coil removes it with everything else and has to be sized for it.
The quieter mistake is counting it twice, once as fan heat and again inside a generous margin. A chilled-water coil sized that way spends most of the year at low valve opening. Its surface runs warmer than the design point, and a warmer coil condenses less water, which in a humid climate is the capacity the room needed.
In dehumidification mode the draw-through case pays back. The air is overcooled to reach its dew point and then reheated, and the 2 K the fan adds after the coil is 2 K the reheat coil does not have to supply. In tropical work reheat energy is a primary design decision, and fan position is part of it.