Months before anyone energises it, a 36 kA breaker on a busbar that can see 38 kA is already drawn on the single-line diagram.
That drawing is where a mechanical engineer can catch an electrical problem early, because the things that go wrong are printed on it. Read it in the direction the power flows:
- A fault level in kA is written at each board. For scale, a 1,600 kVA, 400 V transformer at 6% impedance puts about 38 kA on the main busbar.
- Each breaker's breaking capacity (Icu, IEC 60947-2) and each board's short-time withstand (Icw, IEC 61439) is at or above the fault level at that board.
- Essential loads sit on their own section, with the generator and transfer switch drawn. If the AHUs that hold the pressure cascade share a busbar with the office chillers, load shedding has nothing clean to cut.
- Harmonic loads are marked: variable speed drives and EC fan walls, with any filter shown at the board it serves.
- The earthing system is stated, and metering is shown where energy will be reported.
The short-circuit and discrimination study still does the proving. A diagram that fails the first two checks usually means the study has not been done yet.
Mechanical changes are often what dates the diagram: a larger chiller, EC fan walls in place of one fan, a second AHU moved to the generator-backed board. Send them to the electrical engineer when they happen.