One sampling point in a Grade C room takes twice as long as the others to recover, and the first proposal is usually more air.
Take a 60 m³ room at 20 air changes, 1,200 m³/h. Going to 30 air changes means 1,800 m³/h: 50% more supply air to that room, a larger share of the AHU's fan power every hour it runs, and a pressure cascade to rebalance. If the slow point sits behind a tall cabinet or in a corner far from the nearest low-level return, most of the extra air takes the same path as before, and the corner improves only a little.
A smoke study at the slow point usually shows why. Supply air drops from the terminal and heads for the nearest return, short-circuiting past the corner. Air reaches the corner late and weakly, so particles released there linger.
The cheaper fixes change the path. A return grille moved or added near the dead zone often does most of the work on its own. Where the cabinet stands hard against the wall, pulling it forward gives air a path behind it, and the grilles it would otherwise block are worth marking keep-clear on the layout drawing, since a parked trolley or carton stack undoes the fix. After the change, repeat the ISO 14644-3 recovery test at the same points and compare the times.