Why a higher room pressure differential is not safer

  • Life Sciences
  • 1 min read

30 Pa across a 2 m² door leaf is about 60 N, and people prop open the doors they cannot open easily.

Force is pressure times area. Pulling at the handle, opposite the hinges, the operator feels roughly half of that, on top of the door closer. Someone gowned, with a tray in one hand, meets it dozens of times a shift. Sooner or later the door is wedged, and a door wedged open has no differential across it at all.

So adding pascals "for safety" can remove the separation they were meant to protect.

EU GMP Annex 1 (2022) says adjacent rooms of different grades should have an air pressure difference of a minimum of 10 Pa, as a guidance value, and typical design sits at 10–15 Pa. At 10 Pa the air already leaves through a door gap at around 4 m/s, so extra pascals add very little to the separation.

They do add up. Four steps of 30 Pa put the innermost room 120 Pa above the corridor, and that load sits on wall panels, ceilings and door seals all day.

Where a larger step is justified, the door has to be designed for it: a sliding door, a smaller leaf or a powered opener.

How many doors in your cascade have a wedge mark on the floor?