Ten per cent on the load, on the airflow and on the coil multiplies to 1.33, because each margin sits on the one before. The oversized coil runs at part load most of the year, condenses less water, and RH climbs while temperature holds. One named margin and a part-load check avoid it.
An extra 100 Pa of filter resistance on a 10,000 m³/h supply costs about 460 W, roughly 4,000 kWh a year. The cheapest change point comes when the latest month's extra energy cost exceeds the average monthly cost since fitting, filter set included, provided it sits below the manufacturer's maximum final pressure drop.
A timed airflow setback is simple to validate but blind to off-schedule activity. Particle-count-driven airflow follows real use and can save more, but counters and their failure modes join the validated system. Either way, the room must recover to its at-rest limits, pressures stable, before operations restart.
EN 779 F-classes were replaced by ISO 16890 ePM1, ePM2.5, ePM10 and ISO Coarse, with no exact conversion, so a spares line reading F9 leaves each supplier to choose. Re-specify every pre-filter position in the asset register and on the purchase code, and keep HEPA on EN 1822.