Outlet dew point is the last thing to check on a new desiccant dehumidifier. First confirm rotor direction, speed and seals, set and measure the process and reactivation airflows, and prove the heater and rotor interlocks. Then set the reactivation temperature and compare inlet and outlet dew point with the selection.
N+1 on a fan wall datasheet is a claim until one fan is off. Without a backdraft damper, air runs back through the stopped fan, and with six fans the other five must each carry 20% more air with motor headroom to match. A single-fan-off step at FAT shows airflow, currents and recovery time.
IQ verifies installed equipment against its records, so a file reconstructed after delivery delays qualification. Humiley compiles material certificates, weld and passivation records, the witnessed FAT report, O&M manual and spares list while each unit is built, so IQ starts from a complete record.
A wrong fan duty found at FAT means a revised test sheet; found on a live site it can mean a crane and a delayed OQ. A useful hygienic AHU FAT checks dimensions, casing leakage, fan duty, filter seals, control I/O and material records. Every AeroSano unit is FAT-tested and witnessed, with its equipment file compiled during production.