A desk check for the airflow diagram

  • News
  • 1 min read

An airflow diagram is one sheet, and most pressure cascade errors are visible on it before anything is built.

It shows every room as a box with its supply, return and exhaust flows, and every AHU with what it delivers and takes back. That is enough for arithmetic. An hour with a calculator finds what would otherwise show up during balancing.

  1. For each room, supply minus return minus exhaust is the net leakage: air out through the doors, less air in from higher-pressure neighbours. Sign and size have to fit the cascade.
  2. Room supplies add up to the AHU supply, and return plus fresh air equals supply. Fresh air covers the exhaust plus the leakage that leaves the building.
  3. Every filter stage is drawn with its class, at the AHU and at the terminal.
  4. Each damper, flow station and pressure sensor carries a tag that is in the instrument list.
  5. The room pressures printed on the diagram match the cascade drawing and the room data sheets, room by room.

The room sum is where most of it shows. A room marked +30 Pa, the highest in the suite, with supply equal to return has no air left to leak out, and no amount of balancing will produce the pressure. The same sum exposes a corridor that receives leakage from six rooms and has nowhere to send it.