Skip to content

Life Sciences

Energy recovery in once-through potent suites

  • Life Sciences
  • 1 min read

A high-potency suite that cannot recirculate cools and dries every cubic metre of its air from a tropical afternoon, then throws it away.

Recirculation is the biggest energy saving in most cleanroom HVAC, because return air comes back close to room condition. Many potent suites do recirculate through HEPA filters in safe-change (bag-in/bag-out) housings. Others go once-through, because the risk assessment for that compound does not support return air. The supply is then all outdoor air, at the full wet-season dew point of Ho Chi Minh City.

The energy then has to come back another way.

A run-around coil loop carries heat by glycol between two separate coils. Exhaust and supply never meet, which suits containment, though it recovers less than a wheel.

Heat wheels and plate exchangers recover more but open a leakage or carryover path from exhaust to supply. For a potent suite that path usually rules them out, and the containment case should say so in writing.

On outdoor air this wet, more than half of the coil load is latent. Pre-cooling fresh air on a dedicated coil, and reheating with recovered or condenser heat instead of electric heaters, goes after that part.

Our energy modeling targets a 30% reduction in HVAC energy. For a once-through suite, the choice between these options is made on paper, before the ductwork is fixed.

What does your potent suite do with its exhaust heat today?

Industries

Related

More on this subject

Central Vacuum Cleaning

In GMP audits, scrutiny often lands on Cleaning Procedures. Using portable vacuum cleaners in cleanrooms is a red flag. Why? Because the exhaust turbulence from a portable unit disrupts laminar airflow and can aerosolize settled dust,…

InsightRead

Free cooling is a temperate-climate idea

In the wet season, outdoor air at 29 °C and a 26 °C dew point carries about 84 kJ/kg, against about 37 kJ/kg for cleanroom return air at 20 °C / 45% RH. Economiser hours are close to zero; tropical savings come from dehumidification strategy, avoided reheat, fan power and chiller lift.

InsightRead