At the gap under an isolation room door, a smoke tube shows which way the air moves, whatever the pressure monitor says.
A monitor that has read −2.5 Pa for a month may be right. It may also have stopped seeing the room: a kinked sensing tube, a blocked port, a transmitter that repeats its last value.
The CDC guidelines on environmental infection control ask for continuous negative pressure of 2.5 Pa against the corridor, monitored periodically, preferably daily, with audible manometers or smoke tubes at the door or a permanently installed visual monitor, and documented. A daily round, with the door closed, takes a few minutes:
- The monitor reads inside its limits and the alarm has not been silenced. Open the door for a moment and a live monitor moves.
- Smoke from a tube, or a strip of tissue, held at the gap under the closed door is drawn into the room.
- The door closes by itself and the latch catches when the door is let go.
- Both anteroom doors are shut.
- The exhaust fan shows running at the panel, and the result goes in the log with a time and initials.
Step 2 tends to be the first one dropped once a digital monitor is fitted.
Who signs the daily check on your isolation rooms: nursing, or engineering?