Panel temperature rise in a hot plant room

  • Manufacturing & Distribution
  • 1 min read

IEC 61439 assumes the panel sits in air that averages no more than 35 °C over 24 hours. Many plant rooms in Viet Nam run hotter than that.

Temperature rise is one of the design verifications in IEC 61439-1. The assembly is shown to stay within its limits at the standard's normal service conditions: ambient up to 40 °C, with a 24-hour average no higher than 35 °C. A report that passes there says little about a room that sits near 38 °C for most of the afternoon.

Put the panel in an unventilated plant room under a metal roof, next to the chiller, and the thermal margin is used up long before a breaker trips. It shows up later as drives derating on hot afternoons and trips that never repeat when someone checks the next morning.

The standard has a route for this. A hotter room is a special service condition, and IEC 61439-1 expects the user to declare it. Once it is written into the specification, the assembly builder has to agree how the design is verified or derated for it, instead of quoting the default.

For a tropical site the specification should carry the plant room's real 24-hour average, ventilation or a panel cooler sized for the actual losses in the enclosure, and the watt-loss figure of every VFD inside, taken from the drive datasheet and added to the heat balance.