Pressure-test an old AHU casing before ordering the new coil and EC fan wall that will go inside it.

The retrofit is attractive for good reasons. The unit stays on its plinth, the duct connections stay put and the shutdown can be short. But the new parts inherit the casing, usually the oldest thing in the plant room.

Test it against the EN 1886 leakage class a new unit would be bought to, and read the result section by section. Where the casing runs below plant-room pressure, on the suction side of the fan, every gap pulls plant-room air in. In a draw-through unit that can be downstream of the AHU's final filter, so the air joins the supply without passing it. On the pressure side, leaks go outwards and cost airflow and fan power. Worn filter frames and seals let air round the filters whatever the pressure; EN 1886 rates that separately as filter bypass.

With the coil out, look at the rest. Wet or exposed insulation, a drain pan that has corroded or no longer falls to its outlet, rivets and ledges in the airstream all stay after a retrofit. Measure the doors and the route in as well: a coil that only fits by cutting the casing makes it a rebuild.

Either route goes through change control and requalification of the rooms the unit serves.