A pharma HVAC plant in the tropics buys cooling to take water out of the air, then buys heat to warm the same air back up. All year.
The cooling coil takes supply air below its dew point to meet the humidity limit, and the air leaves too cold for the room, so it is reheated. Cooling and heating run together every hour the plant runs. In a conventional plant the chiller rejects its condenser heat at the cooling tower while a boiler, heat pump or electric heater makes the reheat separately.
A heat recovery chiller keeps the condenser heat. Condenser heat equals evaporator load plus compressor work, so a machine delivering 1,000 kW of cooling at a COP of 5 draws about 200 kW and rejects about 1,200 kW. Part of it goes to the reheat coils as warm water.
The cost is lift. Condensing hot enough for reheat raises the compressor's pressure ratio. The ideal (Carnot) cooling COP between 6 °C evaporating and 37 °C condensing is about 9.0; at 50 °C condensing it falls to about 6.3, roughly 30% lower. Designing the reheat coils for low water temperatures keeps that penalty down.
Where reheat runs only a few hours a day, the lost COP usually outweighs the recovered heat. A tropical GMP plant with reheat running most hours is the case the machine suits.
We count reheat energy in the HVAC energy model at design stage, before the chillers are chosen.