Split units give a 15–25 °C store cheap redundancy and very little say over humidity.
That trade decides most GDP warehouse cooling in Viet Nam. The store has to hold 15–25 °C through the hottest afternoons, and in this climate insulation alone will not do it. So there is active cooling, and the choice usually comes down to DX split units or an air handling unit on chilled water.
Split units win on redundancy and first cost. Each unit fails on its own, one spare covers a breakdown, and any HVAC contractor can repair one. They lose on air distribution and moisture. A wall or cassette unit throws air a limited distance, the top of 7.5 m racking sits in its own warm layer, and every compressor cycles on room temperature. In the wet season the coil stops drying whenever the thermostat is satisfied.
A chilled-water AHU does the opposite. Ducted supply reaches the top levels, the coil can run for dew point with reheat when a product label carries a humidity limit, and the filters sit in one place. Redundancy costs more: a second chiller and pump, or two AHUs sharing the load, and water pipes routed away from the racking.
Our rough rule: a small store with no humidity limit on its labels is well served by splits plus a spare. Add a humidity limit or tall racking and we would put the money into the AHU.
Industries




