NMP's lower explosive limit is about 1.3% by volume, and that figure sets the exhaust flow of an electrode coating oven.
Solvent ovens are normally ventilated to stay below 25% of the LEL, or up to 50% with continuous LEL monitoring on the exhaust (NFPA 86). At 25%, the exhaust can carry no more than about 0.325% NMP by volume.
A hand figure shows the scale. An oven evaporating 100 kg/h of NMP (molar mass 99.1 g/mol) produces about 1.0 kmol/h of vapour, roughly 24 m³/h at 20 °C. Diluted to 0.325%, that needs around 7,500 m³/h of exhaust. The real figure comes from the line's evaporation rate and the standard's temperature correction.
That exhaust goes to recovery, where the NMP is condensed or scrubbed into water and sent back for purification. The HVAC question is the air that replaces it. If the oven draws make-up from the coating hall, the hall goes negative, and on many layouts it sits next to the dry room. The air that fills the gap is then dry-room air, dried to a very low dew point at real cost.
The make-up supply, its dew point and the pressure step between hall and dry room therefore need sizing with the process team, from the same evaporation figure.
Humiley designs Li-ion dry rooms to −60 °C dew point and below, and the coating-hall interface belongs in that design basis.