Recirculation: the heat recovery you already own

  • News
  • 1 min read

The cheapest air a cleanroom AHU handles is the air it has already cooled and dried.

Recirculated air comes back close to room condition. It needs almost no moisture removed.

Fresh air in Viet Nam's wet season is the opposite. In one worked example, cooling and drying 10,000 m³/h of wet-season outdoor air down to a typical cleanroom supply dew point takes about 186 kW of coil load. Most of that is moisture. The same flow of recirculated air needs a small fraction of it.

So the largest heat recovery device in the building is the return duct. Every m³/h of fresh air you do not need saves more than a wheel or run-around coil will recover from the air you do take in. In GMP rooms a wheel also brings a cross-contamination question you then have to answer.

The avoidable fresh air usually hides in four places. Exhaust set higher than the process needs. Leaky construction, so the AHU makes up for gaps with outdoor air. Room pressures set above what the cascade requires. And 100% fresh air chosen by habit for rooms that do not need it.

Some rooms do need once-through air: potent compounds, solvents. Decide room by room, in the design basis, with the reason written down.

Our energy modeling targets a 30% reduction in HVAC energy, and the first line we examine is fresh air.

Related

More on this subject

Two envelopes for a cleanroom HVAC tender

Score the technical envelope of a cleanroom HVAC tender and sign it off before any price is opened. Issue the scoring sheet with the tender: mandatory items pass or fail, the rest weighted, for example 40% technical depth and 20% each for documentation, delivery and service. Score every listed deviation.

InsightRead

Set a device assembly room's class from the product's risk

ISO 13485 §6.4.2 asks for documented contamination control without naming a cleanroom class. Setting the class from sterilisation method, patient contact and bioburden sensitivity often lands device assembly at ISO 8, with ISO 7 only where needed, less air than Grade C, a smaller AHU and a reason an auditor can read.

InsightRead

Energy savings and the requalification bill

Energy measures that change validated cleanroom conditions go through Annex 15 change control. Classification alone can mean 10 sample locations for a 50 m² room, at rest and in operation, before recovery tests and a CCS update. Price that next to the kWh, or design reduced modes in and qualify them once.

InsightRead