Put the same drive in a 45 °C plant room instead of a 35 °C one and it lasts roughly half as long.
That is the 10-degree rule capacitor makers publish: each 10 K rise in operating temperature about halves the expected life of an electrolytic capacitor, and winding insulation ages in a similar way. It is a rule of thumb; the real curve is on the component datasheet.
Variable speed drives, EC fan electronics and 24 V power supplies all depend on those capacitors. They rarely fail on the hot day itself. They fail early, and the report says "drive fault" with no mention of temperature.
IEC 61439-1 gives the normal indoor service condition for a panel as ambient air up to 40 °C, with a 24-hour average of no more than 35 °C. A rooftop plant room in the dry season can sit above that average for weeks, and the air inside the enclosure is hotter than the room.
The cheap protection is a number on the maintenance round. Read the temperature inside the panel, write it down, and look at the fan filters while the door is open. If the readings stay high, ventilate or cool the panel before replacing the drive a second time.
What does the inside of your hottest panel read at 2 p.m.?