After a cold spell in northern Viet Nam, warm humid air arrives while floors and stored goods are still cold. Air at 20 °C and 90% RH has a dew point of about 18.3 °C, so a 15 °C slab gets wet. Extra ventilation adds more of the same air; dry the air or warm the surface.
Air in a ceiling void has never passed a HEPA filter. If the void sits above room pressure, leaks bring it down past light frames and HEPA collars. Keep one void at or below the lowest room under it, seal duct joints, and measure room-to-void pressure at commissioning.
Wind-driven rain past a plain louvre soaks the first filter stage of a fresh-air AHU. A 10,000 m³/h intake needs about 1.4 m² of louvre at 2.0 m/s, or 2.8 m² at 1.0 m/s, and the slower louvre admits less water. Add a drained plenum, a cleanable screen and an ISO Coarse first stage.
A 3 m/s supply jet near a pressure tap can shift the reading by up to about 5 Pa, down or up depending on its angle, which is a third to half of a 10–15 Pa cascade. Tap position, tubing without low loops, matched tube lengths and a still reference port decide whether a room pressure trend is trustworthy.
Pure water has a resistivity of 18.18 MΩ·cm at 25 °C because its own ions conduct, so no treatment plant can deliver more. That is 0.055 µS/cm, against 1.3 µS/cm for the USP Purified Water stage 1 limit. Resistivity sees only ions, so UPW specifications add TOC, particles, dissolved oxygen and silica.