The worst condensation in a northern warehouse often arrives after the cold spell, not during it.

Anyone who has worked through a humid spell in the north of Viet Nam knows the sight: floors sweating, walls streaked, cartons going soft. The physics is simple. For days the slab, the walls and the stored goods have been cooling down. Then the wind turns, and warm, wet air arrives faster than that mass can warm up. Wherever a surface is colder than the air's dew point, water condenses on it.

A worked example: air at 20 °C and 90% RH has a dew point of about 18.3 °C. A floor slab still at 15 °C sits more than 3 K below that, so it gets wet, and it stays wet until either the slab warms or the air dries.

The instinct is to open the doors and run the extract fans. That brings in more of the same air and usually makes it worse. Unconditioned corridors and warehouses see it first because nothing controls either side of the equation.

There are two levers, and they can be combined. Lower the air dew point below the coldest surface: close the building up and dehumidify. Or raise the surface temperature: heat the space or the slab so surfaces stay above the dew point. For GDP storage the choice also depends on what the product label allows.