The air above a cleanroom ceiling has never been through a HEPA filter.
It sits among ducts, cable trays and the backs of light fittings, separated from the room by panel joints and dozens of penetrations, each sealed as well as the installer managed that day. Whether that air stays up there depends on one thing: the pressure of the void relative to the room.
With the room higher, every leak runs from room to void and carries filtered air out. That costs a little supply airflow. With the void higher, the same leaks run the other way and bring unfiltered air down past light frames and HEPA housing collars.
Voids end up positive more often than drawings suggest. Leaking supply duct joints pressurise them. So does a void that opens to a plant room, or to an outside wall facing the wind. And one void spanning rooms at 30, 15 and 0 Pa has to sit at or below the lowest of them, or it feeds the 0 Pa room from above.
The fixes are ordinary: seal and leak-test the duct joints, vent the void to an unclassified space at a known pressure, and put a room-to-void pressure check into the commissioning scope so the direction is measured rather than assumed. We coordinate the void, its vents and its penetrations in the BIM model before the ceiling panels are cut.