A passing floor and passing heel grounders do not prove the operator is grounded. IEC 61340-5-1 and ANSI/ESD S20.20 treat the path from person to ground as a system, with a wrist strap system below 35 MΩ. Qualify footwear and flooring together, then check ionisers, garments and the RH band.

InsightRead

In a fab, the yield report is the slowest sensor

Filtration, AMC control, ±2% RH micro-environments and UHP utilities can each drift without an alarm. Designing facility monitoring with them, measuring at the tool, trending utilities and power on one time base and setting alert limits inside action limits, shows drift before the yield report does.