A 1,000 m² fab bay with fan filter units over 90% of its ceiling carries about 1,250 of them, if each unit is 1,200 × 600 mm.
After handover that is 1,250 EC motors reporting to the BMS, and somebody has to write down what a stopped fan means. With working neighbours around it, one unit down in a large bay can be a work order. Two adjacent units down over a process tool probably deserve an alarm. The integrator can only program that logic if the design documents give it, with the units already grouped by tool and by zone on the drawings.
The count follows from the airflow. ISO Class 1 to 3 spaces need downward unidirectional air over most of their area, at a face velocity usually quoted between 0.3 and 0.45 m/s. At 0.45 m/s one unit moves about 1,170 m³/h. Ducting that from central air handlers would take huge ducts, so the air recirculates: down through the FFUs, out through the raised floor, back to the ceiling plenum at low pressure. A separate makeup air system handles outdoor air, temperature and humidity.
Two smaller items follow. Filters are replaced tile by tile with a leak test on each, so the spares register is built from the FFU schedule. And the EC motors add harmonics, which belong in the power study from the first load list.