Skip to content

Semiconductor Industry

Fab ceilings: fan filter units in their hundreds

  • Semiconductor Industry
  • 1 min read

A 1,000 m² fab bay with fan filter units over 90% of its ceiling carries about 1,250 of them, if each unit is 1,200 × 600 mm.

After handover that is 1,250 EC motors reporting to the BMS, and somebody has to write down what a stopped fan means. With working neighbours around it, one unit down in a large bay can be a work order. Two adjacent units down over a process tool probably deserve an alarm. The integrator can only program that logic if the design documents give it, with the units already grouped by tool and by zone on the drawings.

The count follows from the airflow. ISO Class 1 to 3 spaces need downward unidirectional air over most of their area, at a face velocity usually quoted between 0.3 and 0.45 m/s. At 0.45 m/s one unit moves about 1,170 m³/h. Ducting that from central air handlers would take huge ducts, so the air recirculates: down through the FFUs, out through the raised floor, back to the ceiling plenum at low pressure. A separate makeup air system handles outdoor air, temperature and humidity.

Two smaller items follow. Filters are replaced tile by tile with a leak test on each, so the spares register is built from the FFU schedule. And the EC motors add harmonics, which belong in the power study from the first load list.

FFUs are part of our equipment range, and our semiconductor scope covers ISO Class 1 to 3 cleanrooms.

What does your BMS do today when one FFU in a bay stops?

Related

More on this subject

Data Integrity

You can have a flawless Grade A cleanroom and the most advanced equipment—but if your operational data (temperature, humidity, differential pressure, batch mixing parameters, etc.) does not comply with ALCOA+ principles (Accurate,…

InsightRead

Grade C through a fab engineer's eyes

To a semiconductor engineer, Grade C at ISO 8 in operation looks loose. EU GMP Annex 1 adds microbial limits: 100 CFU/m³ in air, 50 per settle plate over 4 hours, 25 per contact plate. Rooms wiped with sporicide need floors and joints a fab never had to clean, and a CCS that ties the choices together.

InsightRead