A CCS nobody reviews is only a snapshot

  • Life Sciences
  • 1 min read

Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated, and on many sites that means one meeting a year.

The meeting works from memory, and between meetings the document still describes the site as it stood on the day it was signed. The CCS is also meant to drive improvement, which a filed copy cannot do.

Meanwhile the site changes. A return grille moves during a room modification. An AHU setpoint is changed to save energy at night. The EM program shows counts creeping up in a Grade C corridor, and the investigation finds a transfer route the CCS never mentions. Each change is handled correctly in its own system. None of them reaches the document that is supposed to connect them.

The fix is small and procedural. Add one line to the HVAC change control form, the EM adverse trend review and the deviation closure form: does the CCS still say the right thing? If the answer is no, the CCS update becomes an action with an owner and a date, closed with the change rather than a year later.

An annual review still has a place. It just stops being the only moment anyone opens the file.

We treat the CCS as the organizing document of a facility: airflow, material and personnel flows, barriers, utilities, monitoring and qualification should read as one argument.

How we work from design through qualification

Industries

Related

More on this subject

Annex 1's scope reaches non-sterile plants

The scope of EU GMP Annex 1 (2022) says some of its principles, including the contamination control strategy, may be used for certain non-sterile products such as liquids, creams and ointments. A semi-solids plant that writes a CCS tying room grades, flows, water and monitoring to product risk has an answer for the inspector.

InsightRead

WFI belongs in the Contamination Control Strategy

EU GMP Annex 1 (2022) gives WFI circulation above 70 °C as an example of minimizing the risk of microbial growth. Keeping a loop hot drives the design: ASME BPE dead legs of L/D ≤ 2, turbulent flow to the last user point, planned sanitization and sensors on the return. The CCS should justify all of it.

InsightRead

Contamination Control Strategy

In the past, contamination control was often managed in silos: HVAC handled ventilation, Architecture handled walls/ceilings/floors, and QA handled cleaning procedures. But under the updated EU GMP Annex 1, that approach is no longer…

InsightRead