WHO's 2022 GMP for sterile products (TRS 1044, Annex 2) was drafted in step with EU Annex 1.

A plant aimed at WHO prequalification now starts from the same design choices, and the first is the barrier at the filling line. Both texts favour RABS or isolators around the critical zone and expect the choice to be justified. That choice sets the grade of the room around it. Under Annex 1 a RABS stands in a Grade B background, a closed isolator in at least Grade D and an open isolator in at least Grade C. Background grade drives air change rates, gowning, the number of airlocks and the size of every AHU, so it has to be settled before anyone sizes one.

Then comes the document that explains it all. The WHO text asks for a contamination control strategy, as Annex 1 does, tying premises, airflow, barriers, utilities, monitoring and qualification together with the reason for each decision. Writing it after the drawings are frozen usually means hunting for reasons behind decisions nobody recorded.

A project budgeted against the earlier WHO text (TRS 961, Annex 6) is worth re-checking on both points before it goes to tender.

We write the URS, validation strategy and qualification roadmap in parallel with the design, with the target market fixed in the design basis on day one.

Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)

Industries

Related

More on this subject

Annex 1's scope reaches non-sterile plants

The scope of EU GMP Annex 1 (2022) says some of its principles, including the contamination control strategy, may be used for certain non-sterile products such as liquids, creams and ointments. A semi-solids plant that writes a CCS tying room grades, flows, water and monitoring to product risk has an answer for the inspector.

InsightRead

WFI belongs in the Contamination Control Strategy

EU GMP Annex 1 (2022) gives WFI circulation above 70 °C as an example of minimizing the risk of microbial growth. Keeping a loop hot drives the design: ASME BPE dead legs of L/D ≤ 2, turbulent flow to the last user point, planned sanitization and sensors on the return. The CCS should justify all of it.

InsightRead

Contamination Control Strategy

In the past, contamination control was often managed in silos: HVAC handled ventilation, Architecture handled walls/ceilings/floors, and QA handled cleaning procedures. But under the updated EU GMP Annex 1, that approach is no longer…

InsightRead