A cross-section 10% smaller on an AHU offer for 10,000 m³/h means about 23% more pressure drop across the coil and dampers.
The smaller unit is cheaper to build and fits a tight plant room more easily. Those savings are real, and the cost of them turns up on the fan.
Push the same airflow through 90% of the area and the air moves about 11% faster (1/0.9). Across the coil and the dampers the flow is turbulent, and pressure drop there goes roughly with velocity squared: 1/0.81, about 23% higher.
Put a number on it. If the coil and dampers take 400 Pa at the larger section's face velocity, the smaller section needs about 490 Pa to move the same air. At a fan system efficiency of 60%, those extra 90 Pa or so cost roughly 0.4 kW. For a unit that runs all year, that comes to about 3,800 kWh more every year it stays in service.
Filters add their own increase on top, but a smaller one. Air moves slowly through filter media and its resistance rises closer to linearly with velocity, so the filter pressure drop grows by less than 23%.
When comparing bids, ask each supplier for coil face velocity and for the velocity class of the cross-section under EN 13053, then price the fan energy over the life of the unit before choosing on capital cost.