The exhaust HEPA in a potent-compound suite spends its whole life collecting the compound, and one day a technician has to take it out.
Done like an ordinary filter change, that puts a person at an open housing holding a loaded filter. Bag-in/bag-out housings prevent that, and the choices that make them work are made at design stage.
Before anything is opened, gas-tight dampers upstream and downstream isolate the housing from the duct system.
The change happens through a bag fixed to the housing's bag ring. The used filter is drawn into the bag, which is sealed and cut so a sealed stub stays on the ring, and the new filter's bag goes on over that stub. The ring is never open to the room. Pre-filters in the same housing come out the same way.
Injection and sampling ports let the new filter be leak-tested in place, so nobody reopens the housing to scan it.
Location decides whether this is workable at all. The housing needs clear space to handle the bag, a route out for the waste and a floor that can be cleaned.
In a potent suite this task sits near the top of the maintenance criticality ranking, with a written procedure and trained technicians.