The exhaust HEPA in a potent-compound suite spends its whole life collecting the compound, and one day a technician has to take it out.

Done like an ordinary filter change, that puts a person at an open housing holding a loaded filter. Bag-in/bag-out housings prevent that, and the choices that make them work are made at design stage.

Before anything is opened, gas-tight dampers upstream and downstream isolate the housing from the duct system.

The change happens through a bag fixed to the housing's bag ring. The used filter is drawn into the bag, which is sealed and cut so a sealed stub stays on the ring, and the new filter's bag goes on over that stub. The ring is never open to the room. Pre-filters in the same housing come out the same way.

Injection and sampling ports let the new filter be leak-tested in place, so nobody reopens the housing to scan it.

Location decides whether this is workable at all. The housing needs clear space to handle the bag, a route out for the waste and a floor that can be cleaned.

In a potent suite this task sits near the top of the maintenance criticality ranking, with a written procedure and trained technicians.

Our equipment range includes HEPA boxes and housings, and our maintenance service plans work by criticality, with 24/7 response across Southeast Asia under a maintenance agreement.

Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)

Industries

Related

More on this subject

Maintenance that keeps the validated state

A filter changed on night shift without a leak test turns maintenance into a deviation. GMP maintenance works from criticality bands built on the asset register, planned and corrective work in one system, risk-based requalification and calibration, and 24/7 response across Southeast Asia under a maintenance agreement.

InsightRead

What ends the life of a HEPA filter

EU GMP Annex 1 (2022) asks for an integrity test of final filters at requalification and puts no age on the filter. A terminal HEPA is replaced when a leak cannot be repaired within site limits, when pressure drop reaches the manufacturer's final value, or after damage or wetting. On glass-fibre media, dust loading alone does not lower efficiency.

InsightRead